Application:
The meter is widely used for monitoring the inline HOCL, free chlorine, and chlorine dioxide of industrial process water disinfection. The fields including: Municipal water trentrment, drinking water project reform, reserve pool or secondary pressure tank and water recycling disinfection, free chlorine of pool water, fruit and vegetable disinfection sterilization, clinical blood dialysis, medical care, wastewater disinfection and scientific research.
Features:
Electronic chemical inline measurement +sensor +PLC + professional software =system integration
Monitoring the Inline free chlorine, Chlorine dioxide and the concentration of chlorine in water
Control dosing to reduce the waste of reagents and second pollution
Inline monitoring the free chlorine, meanwhile, monitoring the pH value to increase disinfection effect
Driving solutions for various dosing pumps, Static switch, and PWM pulse selection
Dosing tank low level alarm avoids dosing error
Multi-function sampling flow device needs only a little sample
Model: POP-6903
Case materials: ABS+PC
Installation: wall mounted or bottom instllation
Protection level: IP65 (water proof nut wire in≥5mm)
pH meament: pH measurement:pH sensor
pH range:2.0~12.0
resolution:pH: 0.02
Accuracy: pH: ± 0.2
stability:±0.06/24h
temperature:0~40℃
Free clorine/chlorine dioxide measurement:
Sensor material: platinum/ Silver chloride, none membrane sensor
Free chlorine Range:0.20~5.00ppm(mg/L)
Chlorine dioxide Range:0.20~5.00ppm(mg/L)
Measurement accuracy:±5%FS(0.01~2.00ppm); ±10%(2~5.00mg/L)
Measurement Sensitivity:0.01ppm[≤5.00ppm(mg/L)]
pH range:5.0~8.0
temperature range:0~40℃
temperature measure:
built-in free chlorine sensor
Accuracy:±0.5℃
Range:0~50℃
Resolution:0.1℃
Stablility: ±5℃/24h
Switch signal input:
Pull-up voltage12VDC,photoelectricity seclusion
Dosing tank, Low level switch of pool
(or other normal open digital switches): double channels.
Switch signal output:
Relay output:3 channels
Dry Contact output, load capacity, 3A/AC 240V (max.) 3A/DC 30V Max.
OC output:2 channels
load current 25mA(at DC5V),load voltage DC24V(max.)
Analog Conmmnication:
4-20mA output
Double channels, isolated, configuration,transferable, reversible, inside/outside power
supply selectable .max. loop impedance 300oHm, accuracy<±1%
Communication port: RS-485 Serial interface,one channel
Interface:
240x160 LCD display,backlight white/green settings,
six digits graphics button
Working enviroment: temperature:0~60℃ humidity ≤90%RH
Power supply: AC/DC 18V -36V Power consumption ≤10W
Dimension: 235mm×185mm×119mm (H×W×D)
Weight: ≤ 5kg
|
??????? ???????? ?????? ?????